Preventive Maintenance Programs for
STATIONARY FLOODED BATTERY SYSTEMS |
Monthly |
Quarterly |
- Annual - (or initial visit) |
| |
|
|
|
|
Record charging sys mfg./model, serial no., output rating, and
current & voltage reading as displayed on charger |
á |
á |
á |
|
Measure and record battery string current and voltage (metered
reading for each battery string) |
á |
á |
á |
|
Measure and record voltage from most positive to ground and from
most negative to ground |
á |
á |
á |
|
Measure and record AC ripple current going into battery |
á |
á |
á |
|
Measure and record ambient temperature |
á |
á |
á |
|
Inspect electrolyte levels and add to levels when required |
á |
á |
á |
|
Measure and record pilot cell float voltage, specific gravity
and electrolyte temperature |
á |
á |
á |
|
Inspect battery, rack, floor, and battery area and clean as
necessary (battery jar surface cleaned every other quarter
unless needed quarterly) |
á |
á |
á |
|
Inspect for cracks in cells, leakage, and terminal or rack
corrosion |
á |
á |
á |
|
Measure and record the specific gravity of each cell/unit
corrected to 77 degrees Fahrenheit |
|
á |
á |
|
Measure and record the voltage of each cell/unit |
|
á |
á |
|
Measure and record the total voltage of the system |
|
á |
á |
|
Measure and record the electrolyte temperature of each cell/unit |
|
á |
á |
|
Visually inspect each cell/unit in detail (plates, posts,
internal straps, sediment, dust covers, jars, spark arrestors,
vent caps, felt pads, gravity tubes) |
|
|
á |
|
Visually inspect each connection |
|
|
á |
|
Measure and record internal battery resistance and connection
resistance for all cells and electrical connections |
|
|
á |
|
Measure and record torque values of each electrical connection
and correct per manufacturers specifications when necessary |
|
|
á |
|
Inspect the integrity of the battery rack (spot-check torque on
battery rack frames, brace and tie rods, etc.) |
|
|
á |
|
Confirm and record the presence of safety equipment, product
labels as supplied by the mfg., operating manuals, etc. |
á |
á |
á |
|
Review records maintained by customer for periodic log entries |
á |
á |
á |
|
Record date of cleaning and inspection |
á |
á |
á |
|
Provide completed inspection report |
á |
á |
á |
| |
|
|
|
|
* Above items are based on IEEE standard 450 for maintaining
battery systems |
|
|
** All items above focus on verification of Battery System
Uniformity. These tests are not executed to determine battery
capacity however, can be used as a health measure to determine
confidence levels that the battery will perform per
manufacturers current discharge ratings. |
|
*** Capacity testing should not be run unless the batteries'
operation is questionable. Batteries should not be discharged
beyond the specified final voltage. Load testing or capacity
tests are considered a cycle on the battery. Cycling of a
battery will shorten the life of the battery. |